3. Install ornament panel on indoor unit.
Tighten screws to redrce the thickness of seals
between ornament
and indoor unit to 5-8mm.
If indoor unit is at horizontal level and water drainage is
smooth, then, indoor unit height can be adjusted throrgh
holes at corners of ornament panel.
If screws are not tighten tight, problems in Fig.3 might
occur.
Tighten screws properly.
If there are still space after tightening of screws,
please readjust the height of indoor unit.
Gas leakage.
Gas leakage
from roof.
Contamination
Mist exists and drop down.
For indoor unit installation, please refer to Installation Manual.
2. Mounting on high ceiling
If connecting is not made, error code (A7) appears
on remote controller. So, make proper connecting.
Side of ornament panel
Side of indoor unit
Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension
of the ceiling opening is correct. Take off the lever gauge before install the ornament panel.
Fasten the screws to make the height difference between the two sides of
indoor unit less than 5mm.
First fix it with screws temporally.
Fasten the two temporally fixing screws and other two, and tighten the
four screws.
Connect the wires of synchro-motor.
Connect the wire of signal.
If no response of remote controller,check whether the wiring is correct,
restart remote controller 10 seconds after shut off power supply.
Swing motor
Where the swing motor locates in the figure of panle just is the location
of liquide pipe.
Caution
23
Seal
Indoor unit
Ceiling material
Ornament panel
5
_
8mm
Leave no space.
Installation Procedure
Electric control box