9. Failure code and troubleshooting
9.1 Failure code
For the inverter unit with new wired controller YR-E12 (0010451521E)
Number of
flashes of
remote
control and
indoor lights
Wire
control
readout
Centralize
d control
readout
Fault description Possible cause Remedy Purpose Items to be checked
10 08 21 Fault in drain system Float switch is disconnected
25min or longer.
Restorable when given
corrective signal.
To prevent condensate
spilling out of drain pan
Water line, water pump,
float switch, I/O voltage
1 01 01 Fault in indoor
ambient temperature
sensor
Sensor is open-circuit or
short-circuit for 2min or
longer.
Restorable when given
corrective signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
2 02 02 Fault in indoor coil
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or
longer.
Restorable when given
corrective signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
3 4A 11 Fault in outdoor
ambient temperature
sensor
Sensor is open-circuit or
short-circuit for 2min or
longer.
Restorable when given
corrective signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
4 49 12
Fault in outdoor coil
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or
longer.
Restorable when given
corrective signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
5 48 10
Overcurrent Detected CT current is
above the limit three times
within 30min.
Restorable after repair. To prevent overload
(electric parameter).
Power supply, wiring,
compressor, pressure
6 53 14
Fault with high
pressure
High pressure switch is
activated three times within
30min.
Restorable after repair. To prevent overload
(pressure parameter).
Wiring, circuit, pressure
switch, refrigeration
system
Power failure Wrong phase, phase failure
or phase loss.
Restorable after repair. To ensure power supply. Wiring, control board,
power supply
8 07 06 Communication error
between wire control
and indoor unit
Communication error lasts
4min or longer.
Restorable when given
corrective signal.
To ensure transmission to
and from control board.
Wiring, circuit,
transmission voltage
9 06 05 Communication error
between indoor and
outdoor units
Communication error lasts
4min or longer.
Restorable when given
corrective signal.
To ensure transmission to
and from control board.
Wiring, circuit,
transmission voltage
11 0B 30 External alarm signal
input
External signal is cut out for
10s or longer.
Restorable when given
corrective signal.
To control external
connection provided for
building.
External signal, wiring,
control board
12 03 20 Fault in outdoor
coil/suction line
sensor
Sensor is open-circuit or
short-circuit for 2min or
longer.
Restorable when given
corrective signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
13 0D 31 Temperature shut-off Directional valve malfunction
repeats three times.
Restorable after repair. To prevent malfunction of
four-way valve.
Sensor, four-way valve,
system, control board
7 47 22
-167-